ANALISIS KAPASITAS PENDINGINANPRECISION AIR CONDITIONING DI RUANG DATA CENTRE SKK MIGAS JAKARTA

R. Ivan Saputra , Enang S. Arifiyanto
Abstrak
ABSTRAK
Tujuan utama penelitian ini adalah untuk mengetahui penyebab terjadinya temperatur yang cukup tinggi pada ruang data centre SKK Migas Jakarta dan memperoleh beban pendinginan ruangannya. Penelitian ini difokuskan pada analisis beban pendinginan ruangan, analisis kapasitas pendinginan dua unit precision air conditioning, dan kesesuaian antara beban pendinginan ruangan dengan kapasitas pendinginan precision air conditioning. Hasil analisis menunjukkan bahwa terjadinya temperatur yang cukup tinggi pada ruang data centre disebabkan beban pendinginan ruangan sudah melebihi batas kapasitas pendinginan dua unit precision air conditioning. Beban pendinginan ruangan mencapai 459.358,7Btu/h, sedangkan kapasitas total precision air conditioningyang ada hanya 382.580 Btu/h.Total beban pendinginan yang tidak tertangani adalah sebesar 76.778,7 Btu/h. Solusi untuk menanggulangi hal ini adalah dengan menambah minimal satu unit precision air conditioningyang memiliki kapasitas 78.800 Btu/h.

Kata kunci: Precision air conditioning, kapasitas pendinginan, high temperature.


ABSTRACT
The primary objective of this study is to determine the cause of a high enough temperature in the data center space and obtain SKK Migas Jakarta office cooling loads. This study focused on the analysis of the room cooling load, the cooling capacity analysis of two precision air conditioning units, and the fit between the cooling load of the room air with a cooling capacity of precisionair conditioning. The analysis showed that the temperature is high enough in the data center space, due to the cooling load exceeds the capacity of the room had two cooling units precision air conditioning. Room cooling load reached 459,358.7 Btu/h, while the total capacity of the existing precision air conditioning only 382 580 Btu/h. The total cooling load is not handled by 76778.7 Btu/h. The solution to overcome this is to add at least one precision air conditioning unit which has a capacity of 78,800 Btu/h.

Keywords: Precision air conditioning, cooling capacity, high temperature.

Kata kunci : Precision air conditioning, kapasitas pendinginan, high temperature